Real power
P
The power an AC circuit actually converts: rms voltage times rms current times the power factor cos φ. With cos φ = 1, as in a heater, it is plain U·I.
P=1,840W
P equals (230 times 10) times 0.8, equals 2,300 times 0.8, equals 1,840 W
Den här sidan finns på svenska. Byt till svenska
Definition — what does that mean?
The power that actually becomes heat, light or motion — voltage times current times the power factor.
In Swedish: Aktiv effekt
P
The power an AC circuit actually converts: rms voltage times rms current times the power factor cos φ. With cos φ = 1, as in a heater, it is plain U·I.
P=1,840W
P equals (230 times 10) times 0.8, equals 2,300 times 0.8, equals 1,840 W
You are given
U and I are the rms voltage and current, cos φ is the power factor and P the real power in
watts. Many English books write the voltage as V, so the formula reads P = V·I·cos φ. A motor drawing
10 A from 230 V at cos φ = 0.8 converts 230 · 10 · 0.8 = 1,840 W.
Holds when U and I are rms values of a sinusoidal alternating current and φ is the phase difference between them.
U·I alone is the apparent power in volt-amperes. The power factor says how much of it is converted:
| Load | cos φ | U · I | P |
|---|---|---|---|
| Kettle | 1 | 2,001 VA | 2,001 W |
| Motor | 0.8 | 2,300 VA | 1,840 W |
| Motor, lightly loaded | 0.6 | 2,300 VA | 1,380 W |
For a purely resistive heater cos φ = 1, and the formula becomes the familiar electric power P = U·I. That is why U·I gives the right answer for a kettle and too much for a motor.
The kettle. 8.7 A at 230 V and cos φ = 1: P = 230 · 8.7 · 1 = 2,001 W.
A workshop machine. 6.5 A at 230 V with cos φ = 0.85: P = 230 · 6.5 · 0.85 = 1,270.75 W, while the apparent power is 1,495 VA.
The current from the power. A 1,840 W motor at 230 V with cos φ = 0.8 draws I = 1,840 / (230 · 0.8) = 10 A — not the 8 A that 1,840 / 230 gives.
The power factor from a measurement. A meter reads 1,380 W, 230 V and 10 A: cos φ = 1,380 / 2,300 = 0.6.
Where does the power factor come from?
Coils and capacitors make the current fall out of step with the voltage. In an RLC circuit cos φ is the
resistance divided by the impedance, see power factor.
Does a household pay for watts or volt-amperes?
A household electricity meter normally counts energy in kilowatt hours, that is real power times time.
| Solve for | Rearranged | With the numbers | Comes to |
|---|---|---|---|
| U | PIcos φ | 1,84010·0.8 | 230 V |
| I | PUcos φ | 1,840230·0.8 | 10 A |
| cos φ | PUI | 1,840230·10 | 0.8 |
| P | UIcos φ | 230·10·0.8 | 1,840 W |
Last reviewed October 6, 2026 ·How pages are reviewed
Copy the code into your page where the formula card should appear. It loads from lovetocalc.com, so it stays current on its own — all we ask is that the credit line comes with it.