Enter the power, the voltage and the power factor — get the current in amps for single phase or three phase, or turn it round.

Your numbers

Common voltages (examples)

Work out
Supply
Power given in

kVA is apparent power: the current then does not depend on the power factor.

In the unit above.

Single phase: between line and neutral. Three phase: between two lines. 230 and 400 V are nominal supply voltages (IEC 60038), shown only as examples; type your own.

1 for heaters and kettles, lower for motors and transformers. 1 is only where the field opens; a rating plate may state the real one.

Result

Current, amps

10

Real power, kW
2.3
Apparent power, kVA
2.3

A load of 2,300 W at 230 V and a power factor of 1 draws 10 A.

Single phase: P = U · I · cos φ. Three phase: P = √3 · U · I · cos φ, with U the voltage between two lines and equal load on all three. P is real power in watts; apparent power is S = U · I (single) or √3 · U · I (three phase) in volt-amperes. The calculator does not say which cable, fuse or installation is allowed; a qualified electrician decides that. The power factor cannot be worked out from an apparent power.

What this answers

The label on an appliance says watts; a fuse or a cable is spoken of in amps. They are linked by the voltage and, for anything with a motor or a transformer, the power factor. The calculator converts in either direction, for a single-phase or a three-phase supply, and can solve for the voltage or the power factor instead.

Formula

Single phase: P = U × I × PF

Three phase: P = √3 × U × I × PF

Apparent power: S = U × I (single phase), √3 × U × I (three phase)

Worked examples

A 2,300 W heater at 230 V. The power factor of a heater is 1: 2,300 / 230 = 10 A.

The same power with a power factor of 0.8. 2,300 / (230 × 0.8) = 12.5 A.

11 kW at 400 V, three phase. 11,000 / (√3 × 400) = 15.88 A in each line.

10 kVA at 230 V. Apparent power ignores the power factor: 10,000 / 230 = 43.5 A.

What this doesn’t cover

Common questions

Why is the three-phase formula different? Three lines share the load, and the voltage between two of them is √3 times the voltage from a line to neutral. That factor is the difference.