Apparent power
S
The rms voltage times the rms current in an AC circuit, in volt-amperes. It is what the wiring has to carry; the real power in watts is this times the power factor.
S=2,300VA
S equals 230 times 10, equals 2,300 VA
Den här sidan finns på svenska. Byt till svenska
Definition — what does that mean?
Voltage times current on AC — in volt-amperes, not watts.
In Swedish: Skenbar effekt
S
The rms voltage times the rms current in an AC circuit, in volt-amperes. It is what the wiring has to carry; the real power in watts is this times the power factor.
S=2,300VA
S equals 230 times 10, equals 2,300 VA
You are given
U is the rms voltage in volts, I the rms current in amperes and S the apparent power in
volt-amperes, VA. Many English books write the voltage as V, so the same formula reads S = V·I. A machine
drawing 10 A from 230 V has an apparent power of 230 · 10 = 2,300 VA.
Holds when U and I are rms values of a sinusoidal alternating current. On direct current U·I is the whole power, and the difference between VA and W disappears.
On AC the current can run out of step with the voltage, in a motor or a fluorescent fitting for example. Then only part of U·I becomes heat, light or motion. That part is the real power in watts:
where cos φ is the power factor. The units are the same underneath — a volt-ampere is a volt times an ampere, just as a watt is — but the name says which of the two quantities it is.
| Load | cos φ | S at 230 V, 10 A | P |
|---|---|---|---|
| Heater | 1 | 2,300 VA | 2,300 W |
| Motor | 0.8 | 2,300 VA | 1,840 W |
| Motor | 0.6 | 2,300 VA | 1,380 W |
Cables, fuses and transformers are heated by the whole current, however much of it does useful work. They are therefore sized by the apparent power, and a transformer is rated in kVA.
The current from a rating. A UPS rated 1,500 VA at 230 V can carry 1,500 / 230 ≈ 6.5 A.
A workshop machine. 6.5 A at 230 V: S = 230 · 6.5 = 1,495 VA. With cos φ = 0.85 the real power is 1,270.75 W.
What is reactive power?
The part of S that flows back and forth between the source and the load without being converted. It is
measured in var and equals S · sin φ. S, P and the reactive power form a right triangle.
Why are transformers rated in kVA?
The maker does not know what load will be connected. What the transformer can take is a certain current
at a certain voltage, and that is apparent power.
| Solve for | Rearranged | With the numbers | Comes to |
|---|---|---|---|
| U | SI | 2,30010 | 230 V |
| I | SU | 2,300230 | 10 A |
| S | UI | 230·10 | 2,300 VA |