Definition — what does that mean?

Reactive power

The power that swings between the supply and a circuit's coils and capacitors without becoming heat or work.

In Swedish: Reaktiv effekt

Reactive power

The relation

Q=UIsin φ

The power that swings back and forth between the source and the coils or capacitors of an AC circuit without being converted: rms voltage times rms current times sin φ, in var.

Solve for

Q=1,380var

Q equals (230 times 10) times 0.6, equals 2,300 times 0.6, equals 1,380 var

Working3 steps

Practice questions

You are given

  • Q=257.6var
  • U=230V
  • sin φ=0.28

The formula

U and I are the rms voltage and current, φ the phase difference between them and Q the reactive power in var (volt-ampere reactive). Many English books write the voltage as V, so the formula reads Q = V·I·sin φ. A motor drawing 10 A from 230 V with sin φ = 0.6 has Q = 230 · 10 · 0.6 = 1,380 var.

Holds when U and I are rms values of a sinusoidal alternating current. The calculator works with the size; by the usual convention Q is positive for an inductive load such as a motor and negative for a capacitive one.

sin φ from the power factor

A rating plate usually gives the power factor cos φ, not sin φ. Since sin² φ + cos² φ = 1,

sin φ = √(1 − cos² φ)

With cos φ = 0.8, sin φ = √(1 − 0.64) = 0.6. Enter 0.6 in the calculator, not 0.8.

The power triangle

Apparent, real and reactive power form a right triangle with S as the hypotenuse: S² = P² + Q². The same motor, 230 V and 10 A at cos φ = 0.8:

Power Formula Value
Apparent S = U · I 2,300 VA
Real P = U · I · cos φ 1,840 W
Reactive Q = U · I · sin φ 1,380 var

Check: 1,840² + 1,380² = 3,385,600 + 1,904,400 = 5,290,000 = 2,300².

Worked examples

cos φ = 0.96. A load draws 8 A at 230 V. sin φ = √(1 − 0.9216) = 0.28, so Q = 230 · 8 · 0.28 = 515.2 var. A power factor close to 1 means little reactive power.

From S and P. A machine has S = 1,495 VA and P = 1,196 W. Q = √(1,495² − 1,196²) = √804,609 = 897 var, and sin φ = 897 / 1,495 = 0.6.

Common mistakes

Frequently asked questions

Why does the grid care about reactive power? Reactive power does no work in the load but still needs current in the wires, and that current heats cables and transformers. Motors are therefore often compensated with capacitors, which brings cos φ closer to 1.

What is φ in an RLC circuit? The angle between the resistance and the impedance. cos φ is R/Z, see power factor, and sin φ is (X_L − X_C)/Z.

Looking for another letter? The formula solved for each one
Solved for each letter
Solve forRearrangedWith the numbersComes to
UQIsin φ1,38010·0.6230 V
IQUsin φ1,380230·0.610 A
sin φQUI1,380230·100.6
QUIsin φ230·10·0.61,380 var